Energy Recovery Ventilator with efficient cross-flow core
Accessories (sold separately):
ODD-ERV-TIMER | FAP (Flush Access Panel) | MAD (Mud Access Panel) | PAV-B (Polymetric Air Valve) | SAV (Supply Air Valve) |
Heating | Net Outdoor Airflow | Sensible Recovery Efficiency | Adjusted Sensible Recovery Efficiency (this data is not HVI certified) | Apparent Sensible Effectiveness | Average Power | Net Moisture Transfer |
i | 68.4 CFM | 71% | 74% | 76.6% | 27W | 0.60 |
ii | 100.8 CFM | 66% | 70% | 72.4% | 56W | 0.55 |
iii | 148.7 CFM | 61% | 68% | 70.0% | 157W | 0.49 |
Cooling | Net Outdoor Airflow | Sensible Recovery Efficiency | Adjusted Sensible Recovery Efficiency (this data is not HVI certified) | Apparent Sensible Effectiveness | Average Power | Net Moisture Transfer |
i | 67.8 CFM | 62% | 64% | 71.4% | 28W | 0.62 |
Selecting Installation Site
Mechanical Installation (Ceiling Mount)
To mount the unit to the ceiling, use belts rigidly fixed to a horizontal surface or threaded rods and expansion anchors.
The belt, threaded rods and expansion anchors are not included in the delivery set.