OD-SDS-10

Air pressure sensing switch designed for precise airflow monitoring and timed control in ventilation and HVAC systems.


HIGHLIGHTS

  • Sensing Medium: Air
  • Operating Temperature: -40°C to +70°C
  • Maximum Overpressure: 14 in. W.C.
  • Operating Altitude: Below 500 m
  • Mechanical Life: Minimum 100,000 cycles
  • Protection: Inductive Load and Grounding Protection
  • Mounting Position: Vertical
  • Pollution Degree: 2
  • Overvoltage Category: II
  • Load Compatibility: Suitable for resistive or inductive loads
  • Pressure Setting: Preset vertical setting of 0.03–0.05 in. W.C.; adjustable range of 0.02–0.15 in. W.C.
  • Included Accessories: Air tube, insert probe and screws

ELECTRICAL PARAMETERS

  • Operating Voltage Range: 120V AC, 50/60Hz
  • Electrical Load: 3A@120V AC, 50/60Hz
  • Terminal type: Screw-clamp terminal block; 12-20 AWG
  • Rated Impulse Voltage: 1500V

OPERATIONAL PRINCIPLE

  • Timer Operation: Recycling delay timer with 10 min. ON, 15 sec. OFF cycle.
  • Pressure Sensing Switch Operation: When the differential pressure exceeds the set point, the normally closed (NC) pressure-switch contact opens, signaling the microprocessor that the switch state has changed. The microprocessor then energizes the relay and begins the timing sequence.

PRODUCT SHEETS

Spec Sheet

Instruction Manual

NA