ODD-110-18PB

Multi speed Universal Series DC Motor Fan with built-in adjustable humidity sensor


Description:
  • Three fans in one housing your choice 80-110-140 CFM
  • Built-in adjustable humidity sensor from 30-100%RH at standard
  • All speeds have been individually performance tested and certified by HVI

140CFM

Static Pressure (SP)
0.003 SP 0.058 SP 0.100 SP 0.193 SP 0.252 SP 0.32 SP 0.387 SP 0.448 SP 0.507 SP 0.567 SP
151.3 CFM 150.4 CFM 150.3 CFM 145.6 CFM 146.6 CFM 145.5 CFM 147 CFM 139.6 CFM 114.3 CFM 0.00 CFM

 

 

 

 

110CFM

Static Pressure (SP)
0.001 SP 0.058 SP 0.102 SP 0.166 SP 0.249 SP 0.308 SP 0.366 SP 0.436 SP 0.522 SP 0.558 SP
114.3 CFM 114.5 CFM 115.5 CFM 113.0 CFM 114.0 CFM 112.5 CFM 110.2 CFM 110.0 CFM 109.1 CFM 0.00 CFM

 

 

 

 

80CFM

Static Pressure (SP)
0.001 SP 0.060 SP 0.102 SP 0.182 SP 0.248 SP 0.297 SP 0.358 SP 0.397 SP 0.470 SP 0.527 SP
88.3 CFM 85.7 CFM 82.8 CFM 81.5 CFM 83.5 CFM 82.4 CFM 81.6 CFM 83.3 CFM 81.3 CFM 0.00 CFM
Air Volume (CFM) 80 / 110 / 140
Noise (sones) 0.3 / 0.3 / 0.4
Fan Watts 5.6W / 8.5W / 13W
Duct Diameter 6"
Power Rating 120V /60Hz
Housing Size 11-3/8" x 10-1/2" x 7-5/8"
Grille Dimensions 13" x 13-3/4"

 

Assembly Instructions

  1. Slide hanger bars have been provided,
    which allow the housing to be positioned anywhere between the framing.
    The bars span up to 24 inches and can be used on all types of framing:
    I-joist, standard joist, and truss construction.
    Slide hanger bars onto housing and adjust as needed to fit between framing
     
  2. Extend the hanger bars to the width of the framing.
    Position the ventilator with the bottom edge of the hanger bar tabs are flush with the bottom edge of the framing,
    holding the ventilator in place.
    Secure hanger bars to framing using one screw on each end of hanger bar.
    Select a proper hole and secure the hanger bars together using one screw
     
  3. Install Round Ductwork
    Connect the round ductwork (not included) to the damper / duct connector,
    and run the ductwork to a roof or wall cap (not included).
    Using tape (not included), secure all the ductwork connections so that they are air tight